38XRA professional TRMS Multimeter
Functions • Voltage, current and resistance measurement • Capacitance and frequency measurement • Diode and acoustic continuity test • Attenuation measurement (dBm) • Temperature measurement Device information • Automatic and manual range selection • Integrated measurement memory (data hold) • MIN/MAX, relative and peak value measurement • Additional bar graph display (41 segments) • Illuminated display • Shock-proof and impact-resistant thanks to standard protective holster • Auto power-off • AC/DC true RMS measurement (TRMS) • Magnetic holster (Magne-Grip™) • Duty cycle function • RS-232 interface for PC connection (optional "38SW-A" software available) • Current loop measurement: 4–20 mA
Technical data Display LCD, 4-digit, 9999 Count Mesaurement Ranges Voltage AC 0.1 mV…750 V Tolerance ±(1.2% rdg. + 10 Digits) Frequency Range 45 Hz…2 kHz Voltage DC 0.1 mV…1000 V Tolerance ±(0.25% rdg. + 5 Digits) Input Impedance 10 MΩ Current AC 0.1 µA…10 A Tolerance ±(1.5% rdg. + 20 Digits) Frequency Range 45 Hz…1 kHz Current DC 0,1 µA…10 A Tolerance ±(0.5% rdg. + 10 Digits) Resistance 0.1 Ω…40 MΩ Tolerance ±(1.0% rdg. + 10 Digits) Continuity R < 40 Ω Frequency 3.00 Hz…10 MHz Tolerance ±(0.1% rdg. + 5 Digit) Capacitance 0.01 nF…400,0 µF Tolerance ±(3.0% rdg. + 10 Digits) Temperature -20°C…1300°C Tolerance ±(1.0% rdg. + 3°C) DC Loop Current (4…20 mA) 0 to 100% Tolerance ±(0.5% + 5 Digits) dBm reading -13 dBm to +50 dBm Tolerance ±(0.7 dB + 8 Digits) Pollution Degree 2 Overvoltage Category CAT IV/600 V, CAT III/1000 V Safety DIN VDE 0411, EN 61010, IEC 61010 Power Supply 1 x Battery 9 V, IEC 6LR61 Dimensions 196 x 92 x 60 mm Weight approx. 492 g (incl. Battery) |